• Motortronics (Fairford) VMX-SGY-309 Synergy 230-480V  500 Amp Motor Starter  110v Control

VMX-SGY-309 Motortronics

Factory New

Only 1 left in stock

  • $4,580.00

Fast Delivery!

Manufacturer Warranty!

Secure Checkout!


AFi Inventory Options

Click below to highlight option.

Fast Delivery!

Manufacturer Warranty!

Secure Checkout!

Eco Friendly Option!

Motortronics (Fairford) VMX-SGY-309 Synergy 230-480V 500 Amp Motor Starter 110v Control

VMX-synergy Soft Starter with Internal

Bypass, 480V, 400HP, 477A, Trip Class 10  

VMX-synergy™ Series - Premium Digital Soft starter

Quick Start Guide

Product Selection Guide

Features

• 3.5” Full Color Touch Screen

• 42 Fully Automatic Application Set-up Parameters Programs

• 14 Operation Languages to choose from

• Easy setup in less than one minute

• Built-in iERS - intelligent Energy Recover System

• Full I2T Motor Loaded Protection

• Internally Bypassed

• Life Time Event Logging Diagnostics

Specifications

Designation: 3-phase SCR Energy Saving Motor Controller

Bypass: Internally Bypassed

Motor Protection: Full I²T Motor Overload with memory, Current limit set at 4.5x to meet IEC standards

Supply Voltages: 208, 230, 400, 480 V as standard, Operates varying supply frequency of 45 - 65Hz

Standard Duty Rating: Trip Class 10 3 x 23 or 3.5x 17, 5 starts/hour 90% duty

Enclosure Type: Size 1 to 3: IP00, IP20- with finger guard

Enclosure: Main chassis: Metal

Construction: Front Cover: Injection Molded Plastic, Terminal Covers: Injection Molded Plastic

Terminal Position: Terminal position/spacing to match common contactors

Terminal Construction: Size 1 to 2: Cage Clamp, Size 3: Busbar

Control Voltages: 24V DC, 110/230V AC

Ambient Operating Conditions: -4°F to 122°F (-20°C to 50°C)

iERS Energy Saving Technology: Yes

In Delta/6 wire connection: Yes

Display Technology: 3.5“ Color TFT Touch Screen

Remote Display Keypad: Optional IP55 full color touch keypad available for remote/door fitting

Languages: English, Chinese (Mandarin simplified), French, German, Italian, Japanese, Korean, Polish, Portuguese, Russian, Serbian, Spanish,

Turkish, Vietnamese

Input/Outputs:

- 3 x NO programmable output relays / 1 x NC programmable output relays / 3 x programmable digital inputs / 1 x PTC thermistor input

- 1 x 0-10V/4-20m Analogue input / - 1 x 0-10V/4-20m Analogue output / 1 x USB

Communications: Standard: Modbus, Optional: Modbus TCP, Profibus DPV1, Ethernet/IP

Data Logging:

- Equipped with 4Gb memory, allowing the logging of every event

- Date of first start (warranty date)

- Total number of soft starts / Number of soft stops

- Number of error events / Display event logs

- Export data in CSV format

EU/IEC Legislation: IEC 60947-4-2: 2012 LV Directive

Environmental: Products comply to REACH, SVHC, RoHS and WEEE

Approvals/Standards: CE, ASME, CSA, ETL

Reliability: Fan efficiency detected, logged and reported

Field Serviceability: Firmware upgrade from USB port.