Danfoss 134F4377 (FC-202P7K5T6E66HXXGXXSXSXXXXAXBXCXXXXDX) 7.5HP 9A IP66IP66 VLT Aqua Drive FC-202
The 134F4377 is an optimised drive for AC motor driven water and wastewater applications, with a rated output of 7.5HP, or 9A and running off a Three Phase 525-600V supply.
User friendly comissioning makes installation simple and enables owners to reach the highest level of performance and lowest cost of ownership. The 134F4377 is set up quickly and easily with the user friendly dialogue based Smart Start, and a quick menu. The quick menu provides direct access to the most important parameters for water and pump applications, by collecting these in one place, the risk of incorrect configuration is reduced significantly.
Featuring a large range of powerful, standard features, which can be expanded with performance improving options, the VLT® AQUA Drive is equally suited to both new and retrofit projects. Features such as dry run detection and flow confirmation help to protect your pumps and deragging can be performed as either preventative or reactive cleaning. Motor alternation and cascade controller helps to save energy and reduce equipment costs. These are only a few of the dedicated pumping features of the 134F4377
The 134F4377 is also known as FC-202P7K5T6E66HXXGXXSXSXXXXAXBXCXXXXDX.
As an approved Danfoss service centre, AFi are also able to offer repairs of the 134F4377, along with field service, installation and commissioning support and selection advice. Our experienced team also provide upgrade advice and implementation and control panel design and build.
134F4377 Specifications
AC Drive Brake Chopper | No |
AC Drive Communications | Modbus Comms |
AC Drive Conformal Coating | No |
AC Drive Filter | No RFI Filter |
AC Drive Heavy Duty Output (kw) | 5.5 |
AC Drive Input Voltage (VAC) | 525-600V |
AC Drive Keypad | Yes |
AC Drive Logic | Positive, Negative |
AC Drive Loop | Open Loop |
AC Drive Normal Duty Output (kw) | 5.5 |
AC Drive Nr Analog Inputs | 2 |
AC Drive Nr Analog Outputs | 1 |
AC Drive Nr Digital Inputs | 6 |
AC Drive Nr Digital Outputs | 2 |
AC Drive Nr Relay Outputs | 2 |
AC Drive Phase | Three Phase |
AC Drive Protection | IP66, IP66 |
AC Drive Pulse Input | 2 |
AC Drive Safe Torque Off | No |
AC Drive Heavy Duty Output (HP) | 7.5 |
AC Drive Normal Duty Output (HP) | 7.5 |
AC Drive Heavy Duty Output (Amps) | 9 |