Danfoss 134F6393 (FC-202P1K5T2E66H2XGXXSXSXXXXAXBXCXXXXDX) 2.0HP 7.5A IP66IP66 VLT Aqua Drive FC-202
The 134F6393 is an optimised drive for AC motor driven pumping applications, with a rated output of 2.0HP, or 7.5A and running off a Three Phase 200-240V supply.
User friendly comissioning makes installation simple and enables owners to reach the highest level of performance and lowest cost of ownership. Set up the 134F6393 quickly and easily with the user friendly dialogue based Smart Start, and a quick menu. The quick menu provides direct access to the most important features for water and pump applications, by collecting these in one place, the risk of incorrect configuration is reduced significantly.
Featuring a comprehensive selection of powerful, standard features, which can be expanded with performance improving options, the VLT® AQUA Drive is equally suited to both new and retrofit projects. Features such as dry run detection and flow confirmation help to protect your pumps and deragging can be performed as either preventative or reactive cleaning. Motor alternation and cascade controller helps to save energy and reduce equipment costs. These are only a few of the dedicated pumping features of the 134F6393
The 134F6393 is also referred to as FC-202P1K5T2E66H2XGXXSXSXXXXAXBXCXXXXDX.
As an approved Danfoss service partner, AFi are also able to offer repairs of the 134F6393, along with field service, installation and commissioning support and selection advice. Our experienced team also provide upgrade advice and implementation and control panel design and build.
134F6393 Specifications
AC Drive Brake Chopper | No |
AC Drive Communications | Modbus Comms |
AC Drive Conformal Coating | No |
AC Drive Filter | Class A2 (C3) |
AC Drive Heavy Duty Output (kw) | 1.5 |
AC Drive Input Voltage (VAC) | 200-240V |
AC Drive Keypad | Yes |
AC Drive Logic | Positive, Negative |
AC Drive Loop | Open Loop |
AC Drive Normal Duty Output (kw) | 1.5 |
AC Drive Nr Analog Inputs | 2 |
AC Drive Nr Analog Outputs | 1 |
AC Drive Nr Digital Inputs | 6 |
AC Drive Nr Digital Outputs | 2 |
AC Drive Nr Relay Outputs | 2 |
AC Drive Phase | Three Phase |
AC Drive Protection | IP66, IP66 |
AC Drive Pulse Input | 2 |
AC Drive Safe Torque Off | No |
AC Drive Heavy Duty Output (HP) | 2.0 |
AC Drive Normal Duty Output (HP) | 2.0 |
AC Drive Heavy Duty Output (Amps) | 7.5 |